Home arrow Hardware arrow ipEther232 arrow Connect a Simatic S7 to the Ethernet arrow Without PPI cable

Serial-Ethernet Converter networks a Simatic S7 (PLC) - without PPI cable

Installation and configuration instructions


Hardware components:
Simatic S7-200, test motor (output simulator),
RS485 cable (Sub-D plugs), ipEther232 24V DIN-Rail, 24V power pack, network cable


1. Wiring
  • Mount an connect the RS485 Kabel
  • Connect ipEther232 (Serial-Ethernet Converter) with power pack and network cable (Ethernet)
  • Connect ipEther232 (Serial-Ethernet Converter) to the Simatic S7 with a PPI cable

Cable termination is required for RS485 connections in termination networks in order to enforce quiescent levels on bus systems whenever no data transmitters are active. The termination network is set via jumper blocks 6, 7 and 8 (integrated in the ipEther485 casing). For details concerning pin allocations and jumper settings, please read the sections "Plug assignment" and "RS485 module" in the ipEther232 manual.

RS485 PIN allocation

ipEther232 and SIMATIC S7-200 (PLC) with RS485

2. ipEther232 Configtool parameters
  • The ipEther232 (Serial-Ethernet Converter) must respond to the same IP range as the user PC does. You can change the IP with a right mouse-click on "ipEther_232" -> "Set IP".

Configtool

  • Under "Properties" -> "RS232", select the COM port
  • Select "Half Duplex (RS485)". All other functions in "Properties" -> "RS232" will be hidden automaticly.


RS485 Settings

3. STEP 7 manager parameters
  • Click "Communications" in the left menu
  • "Set PG/PC Interface"
  • At "Interface Parameter Assignment Used:", select "PC/PPI cable(PPI)"
  • "Properties..."
  • Assign COM port at "Connection to:", and deactivate "Modem connection"
  • At "PPI", deactivate "Multi Master Network"
  • Update at ""Communication"

STEP 7 Manager


STEP 7 Manager parameterization (from left to right):
S7 Manager communications
Select "Set PG/PC Interface"
S7 Manager: set PG PC interface
At "Interface Parameter Assignment Used:", select "PC/PPI cable(PPI)":
-> Properties
S7 Manager: properties PC/PPI-connection
Assign COM port at "Connection to:", and deactivate "Modem connection":

S7 Manager: properties-PC/PPI-cable
At "PPI", deactivate "Multi Master Network"
-> Update at "Communication"



4. Programming the Simatic S7 CPU via network (standard proceed)


To the installation and configuration instructions with PPI cable >>


<<
↑